Translate

English French German Spain Italian Dutch

Russian Portuguese Japanese Korean Arabic Chinese Simplified

Sabtu, 05 Mei 2012

Temperature Control MX-V Series


?
 
     * MX-V series
    - Selection of RAMP
  - Multi inputs (11 kinds)
  - P.I.D automatic operation
  - Selection of remote input or local input
 
             
     
     
 

MODEL MX9-V MX2-V
Appearance(mm)
96(W) x 96(H) x 100(D)
48(W) x 96(H) x 100(D)
Function
Multi input, Heating/Cooling PID control, HBA( Heater Break Alarm ), Remote function, Manual output function,
Remote/Local input selectable °C/°F, Reverse/Direct action selectable. Ramp
Power voltage 110 ~ 240VAC ( 50/60Hz )
Power consumption Max. 15VA
Input 11 kinds of input
CT INPUT HBA ( 25.0A or 50.0A )
Control output
Relay contact : AC 250V 5A ( Resistive load ),
SSR : 12V DC ( constant voltage pulse ) [ Load resistance Min. 800Ω ],
Current : 4 ~ 20mA DC ( Load resistance Max 600Ω )
Control action PID ( Auto-tuning function ) or ON/OFF
Alarm output Relay contact output : AC 250VAC 3A ( AL-2 ), 3A ( AL-1 ) Resistive load
Heater / Loop Break Alarm LBA, HBA [ Relay contact output : AC 250, 3A ( Resistive load )]
Setting By Up/Down key on the front
Display L.E.D Display
PV : 8 mm , SV : 8 mm
Setting and display accuracy
T/C : within ±3°C ( 6°F ) [ Whichever is larger ] ,
R.Input : 0 ~ 199°C ( 0 ~ 399°C ) within ±5°C ( 10°F ) ,
R.T.D : within ±2°C ( 3°F ) whichever is larger
Memory protection Semi-permanent
Sampling cycle 500ms
Heating cycle 1 ~ 100sec
Cooling cycle 1 ~ 100sec
Cooling gain Display of 10 times to proportional band
Cooling deadband -20.0 ~ 20.0°C ( °F )
Input correction range SLU ~ SLF
Insulation resistance Min 20MΩ ( DC500V Mega )
Dielectric strength AC 2000V 50/60Hz for 1 minute ( Between terminal and earth )
Vibration Malfunction 2 ~ 55Hz, X,Y,Z each positions for 10 minutes
Durability 10 ~ 55Hz, 0.76mm, X,Y,Z each positions for 2 hours
Shock Malfunction 100m/s² 6 positions each 3 times
Durability 300m/s² 6 positions each 3 times
Life Mechanical Min. 10 millions operations ( Relay type )
Electrical Min. 0.3 millons operations ( Relay type )
Ambient temperature and humidity 0 ~ 50°C ( 32 ~ 122°F )ㆍ35 ~ 85%RH ( No icing )




 

Tidak ada komentar: